CSA CGA 3.16-M88:2014 pdf download.Lever Operated Non-Lubricated Gas Shut-Off Valves
1.11 This Standard applies to manual lever operated, gas shut—off valves of metallic construction, with weld and flanged and threaded ends other than pressure lubricated designs.
1.1.2 This Standard applies to valves used in:a appliances and equipment where gas is to be used For fuel purposes and,piping and tubing systems falling within the pressure limitations covered in this Standard.
1.1.3 This Standard sets forth the minimum capabilities which a valve must possess in order to be considered suitable for use with natural gas, manufoctureci gas and liquefied petroleum gases (distributed as vapour with or without the admixture of air), or mixtures thereof.
Note: Valves covered by this Standard may be used on “digester gas” (methane produced during sewage treatment) but because of entroined contaminants their use shall be subject to agreement between the rnanufacturer and the purchaser.
Valves covered by this Standard may not be used on “sour gas” (gas with entrained hydrogen sulphide) without modification i.e. additional requirements. Manufacturers should be consulted for their recommendation and agreement reached between the manufacturer and purchaser.
1.1.4 Requirements for valves NPS 1/4 to 8 are specified.
1.1.5 This Standard covers valves that ore suitable for use in the services specified in 1.1.6 over a pressure range of zero to 860 kPa (125 psig) and in addition shall withstand field pressure testing to a maximum permssab1e pressure of 1290 kPo (187 psig).
Note: The obturator must not be moved while the valve is at a pressure exceeding the rated maximum operating pressure.
1.1.7 This Standard contains SI (Metric) equivalents to the yard/ pound quantities,the purpose being to al1ow the Standard to be used in SI (Metric) units.If a value for a measurement as given in this Standard is followed by an equivalent value in other units, the first stated is to be regarded as the requirement.The given equivalent may be approx imate.If a value for a mea-surement and an equivalent value in other units are both specified as a quoted mark-ing requirement, the first stated unit,or both shall be provided.
1.3.3 Valve cover or body bolting shall be such that direct nominaI stress does not exceed 60 MPa ( 8700 psi) on the effective direct tensile
stress area of ASTM A193 Grade B7 bolts, or 47 MPa ( 6800 psi) on the fective direct tensile stress area of bolts of other materials assuming a pres-sure of 860 kPa (125 psig) to act upon an area bounded by the effective outside peri-phery of the gasket.
For flat faced gas-kets。the bounding diameter for the bolt stress calculation shall be the bolt circle di ameter.CSA CGA 3.16-M88 pdf download.