ISO 6182-16:2020 pdf download

ISO 6182-16:2020 pdf download.Fire protection一Automatic sprinkler systems
1 Scope
This document defines performance requirements, methods of testing and marking requirements for fire pump relief valves intended to rapidly relieve the excessive water pressure in the supply piping for standpipe systems or sprinkler systems or both. Performance and test requirements for other auxiliary components or attachments to fire pump relief valves are not covered by this standard.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
Iso 898-1, Mechanical properties offasteners made of carbon steel and alloy steel — Part 1: Bolts, screws and studs with specified property classes — Coarse thread and fine pitch thread
ISO 898-2, Mechanical properties of fasteners made of carbon steel and alloy steel — Part 2: Nuts with specified property classes — Coarse thread and fine pitch thread
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at http://www.electropedia.org/
3.1 corrosion resistant material
bronze, brass, Monel®l) metal, austenitic stainless steel, or equivalent, or plastic material conforming with the requirements of this document
3.2 main valve
part of the valve assembly that controls the flow of water
4.1.1
The nominal size of a fire pump relief valve shall be the nominal diameter of the inlet and outlet connections, i.e. the pipe size for which the connections are intended. The sizes shall be 20 mm, 32 mm,40 mm, 50 mm, 65 mm, 80 mm, 100 mm, 125 mm, 150 mm, 200 mm, 250 mm or 300 mm. The diameter of the waterway through the sealing assembly seat ring may be no more than one size smaller than the
nominal size.
4.1.2 Unless otherwise noted in a specific clause of this document, tolerances shall be in accordance with Annex A.
4.2 Connections
4.2.1 All connections shall be designed for use at the rated working pressure of the valve.
4.2.2 The dimensions of all connections shall conform with the applicable requirements of relevant international standards. If international standards are not applicable, national standards may be used.For example, ISO 6182-12 contains requirements for grooved-end components. Where there is not an ISO standard developed, a national standard may be used for other connection types (i.e. threaded, flanged, or other suitable connections).ISO 6182-16 pdf download.